Final | 2/27/2012 | 2/28/2012 | 2/28/2012 | A | PASS |
Jack Frank
|
|
|
Key for front door is in mailbox. Phone #: ###-#### >> Inspection requested via web by Lars Johnson ok called needs gfci unfinished rm. in basement
|
Permanent Service | 2/2/2012 | 2/2/2012 | 2/2/2012 | A | PASS |
Jack Frank
|
|
|
raised guy wire, moved a/c lines Phone #: ###-#### >> Inspection requested via web by Lars Johnson p/s o/h rec. ok
|
Permanent Service | 1/27/2012 | 1/27/2012 | 1/27/2012 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lars Johnson 110.26(F)(2) remove a/c lines from below p/s for required clearence move guy kit up by weatherhead for adequate support of mast 230.28
|
Rough-In Permanent Service | 1/17/2012 | 1/17/2012 | 1/17/2012 | P | NR |
Jack Frank
|
|
|
Electrical rough-in & permanent service Phone #: ###-#### >> Inspection requested via web by Lars Johnson see added r/i, called seal KOs at subpanel, cables shall enter thur connectors at p/s 312.5(C), not short section of pvc
|
Electrical Rough-In | 1/17/2012 | 1/17/2012 | 1/17/2012 | P | PASS |
Jack Frank
|
|
|
Electrical rough-in & permanent service Phone #: ###-#### >> Inspection requested via web by Lars Johnson r/i ok
|
Electrical Rough-In | 1/12/2012 | 1/13/2012 | 1/13/2012 | A | PART |
Jack Frank
|
|
|
lars Phone #: ###-#### exterior walls ok
|
Issue PAID IN FULL permit | | | 1/12/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/12/2012 | | DONE |
|
|
|
This permit was created on the web by Lars Johnson
|