First Notice | 4/4/2012 | 4/4/2012 | 1/22/2014 | | DONE |
Daryl DeGrange
|
|
|
This permit finaled on the web by Clint Tate
|
Final | 4/3/2012 | 4/4/2012 | 4/4/2012 | A | PASS |
Daryl DeGrange
|
|
|
As early as possible please. Thank You Phone #: ###-#### >> Inspection requested via web by Clint Tate final ok bath rooms
|
Electrical Rough-In | 2/29/2012 | 3/1/2012 | 3/1/2012 | A | PASS |
Daryl DeGrange
|
|
|
cover Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover bathrooms and near area
|
Rough-In Permanent Service | 2/1/2012 | 2/1/2012 | 2/1/2012 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in p/s o/h ok
|
Permanent Service | 1/23/2012 | 1/23/2012 | 1/23/2012 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Not all corrections completed
|
Permanent Service | 1/20/2012 | 1/23/2012 | 1/23/2012 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate NEC 250.52(A) (1) Metal underground waterpipe. Grounding electrode conductor shall be sized to 250.66 Sprinkler system bond shall sized per 250.66 also.
|
Issue PAID IN FULL permit | | | 1/17/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/17/2012 | | DONE |
|
|
|
This permit was created on the web by Clint Tate
|