Final | 11/30/2012 | 11/30/2012 | 11/30/2012 | P | PASS |
Daryl DeGrange
|
|
|
Kelly Phone #: ###-#### final ok
|
Final | 10/8/2012 | 10/8/2012 | 10/8/2012 | P | NH |
Daryl DeGrange
|
|
|
kelly Phone #: ###-#### no access
|
Final | 9/27/2012 | 9/28/2012 | 9/28/2012 | A | FAIL |
Daryl DeGrange
|
|
|
kelly Phone #: ###-#### NEC 210.8 all 125 volt single phase 15 and 20 ampere receptacles installed outdoors shall have GFCI protection. All electrical devices shall be install in UL listed enclosure. NEC 406.8(B) All 15 and 20 ampere receptacles installed in wet locations shall be listed weather resistance type. NEC 406.8(A) weatherproof receptacle cover are required
|
Electrical Rough-In | 8/8/2012 | 8/8/2012 | 8/8/2012 | P | FAIL |
Bob Reichert
|
|
|
kelly Phone #: ###-#### changed to #12 conductor, did not make-up, cut conductors short, shall add nailplates, told builder about fail inspection
|
Electrical Rough-In | 8/6/2012 | 8/7/2012 | 8/7/2012 | P | PASS |
Daryl DeGrange
|
|
|
Kelly Phone #: ###-#### rough-in ok cover, covered patio bar
|
Application received | | | 2/8/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 2/8/2012 | | DONE |
Barbara Stitt
|
|
|
|