Final | 6/18/2013 | 6/18/2013 | 6/18/2013 | P | PASS |
Rock A. Hudson
|
|
|
Jerry Phone #: ###-#### Corrections listed made. Final ok
|
Final | 5/31/2013 | 5/31/2013 | 5/31/2013 | P | FAIL |
Rock A. Hudson
|
|
|
210.8 All bath recepticals shall be GFCI protected. Bath receptical still has not been changed. 410.10(A) Light fixtures installed in wet locations shall be listed for wet locations. Light fixture has been installed that is listed for wit locations but a nuetral wire sticking out from light base needs to be correctly installed.
|
Final | 5/8/2013 | 5/13/2013 | 5/13/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Corrections have not been completed. Electrical contractor has not been secured to fix electrical issues. NEC-210.8 All bathroom recepticals shall be GFCI protected. NEC-110.12(A), 314.23(B)(1) All unused openings shall be closed. Plastic single gang box shall not be secured by screws through side wall. NEC-410.10(A) Light fixtures installed in wet or damp locations shall be listed for wet or damp locations
|
ELE-Aging Inspection | 5/8/2013 | 5/8/2013 | 5/8/2013 | P | FAIL |
Doug A Poedy
|
|
|
GFCI in front bathroom. Listed wet location fixture in front bath. Replace plastic box in partition wall..
|
ELE-Aging Inspection | 3/22/2013 | 3/22/2013 | 3/28/2013 | | DONE |
Rock A. Hudson
|
|
|
still under construction
|
Conference | 2/17/2012 | 2/21/2012 | 2/21/2012 | A | PASS |
Daryl DeGrange
|
|
|
conference. Call Doug Asked home to remove lamp cord that is ran through vanity cabnet to an receptacle, replace three wire receptacle in livingroom with no equipment grounding conductor to an two wire receptacle. Anchor receptacle on eastside of partion wall in livingroom
|
Conference | 2/17/2012 | 2/17/2012 | 2/17/2012 | P | CANC |
Doug A Poedy
|
|
|
Per Jenifer GillilanD Rescheduled
|
Override - Parcel Holds | 2/17/2012 | 1/1/1900 | 2/17/2012 | | |
|
|
|
Electrical conference
|
Application received | | | 2/17/2012 | | DONE |
Barbara Stitt
|
|
|
|
Override - Parcel Holds | | | 2/17/2012 | | |
|
|
|
|
Override - Parcel Holds | | | 2/17/2012 | | |
|
|
|
|
Issue & PRINT permit | | | 2/17/2012 | | DONE |
Barbara Stitt
|
|
|
|