Final | 5/2/2012 | 5/3/2012 | 5/3/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey ok final
|
Final | 4/18/2012 | 4/19/2012 | 4/19/2012 | A | FAIL |
Bob Reichert
|
|
|
>> Inspection requested via web by Neal Rumsey called shall provide 2 small appliance branch circuits in kitchen, fix open ground in old garage, provide front receptacle, provide in-use cover rear receptacle
|
Electrical Rough-In | 3/1/2012 | 3/1/2012 | 3/1/2012 | A | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey
|
Electrical Rough-In | 2/27/2012 | 2/27/2012 | 2/27/2012 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, told contractor shall staple nm cable, provide free conductor length, use nailplates, look at panel violations
|
Issue PAID IN FULL permit | | | 2/22/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/22/2012 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|