Fees Due Hold | 2/29/2012 | | 3/12/2012 | | DONE |
Patricia Smith
|
|
|
|
Temporary Service | 2/28/2012 | 2/29/2012 | 2/29/2012 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper t/s u/g new ok
|
Temporary Service | 2/27/2012 | 2/28/2012 | 2/28/2012 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper called correction posted 110.12(B) clean dirt from t/s 110.3(A) replace broken 2 pole gfci breaker, 250.24(A)(1) terminate GEC to neutral bus
|
Reinspection Fee (no hold) | 2/28/2012 | 2/28/2012 | 2/28/2012 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper
|
Application received | | | 2/27/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 2/27/2012 | | DONE |
|
|
|
|