Final | 5/3/2012 | 5/4/2012 | 5/4/2012 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ok final
|
Rough-In Permanent Service | 3/28/2012 | 3/29/2012 | 3/29/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/26/2012 | 3/27/2012 | 3/27/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left message, left correction notice, BCC shall not cover u/g without inspection, framing shall be complete, wiring shall be installed, shall provide available fault current from IPCO at service, NEC 334.23 shall protect cables within 6' of attic access, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member or provide nail plates
|
Issue PAID IN FULL permit | | | 3/26/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/26/2012 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|