ELE-Aging Inspection | 4/30/2014 | 4/30/2014 | 4/30/2014 | | DONE |
Rock A. Hudson
|
|
|
Finalled 1-29-14. I will close permit
|
Final | 4/30/2014 | 4/30/2014 | 4/30/2014 | P | PASS |
Rock A. Hudson
|
|
|
Final ok 1-29-14 by Daryl Degrange
|
Final | 1/29/2014 | 1/29/2014 | 1/29/2014 | A | DONE |
Daryl DeGrange
|
|
|
Idaho Power will be there at 10:00am for shutdown.I''ll replace the bonding hub then and bond the gutter by the hot tub. Phone #: ###-#### >> Inspection requested via web by Kevin Koomler correction done, final ok
|
ELE-Aging Inspection | 1/2/2014 | 1/2/2014 | 1/7/2014 | | DONE |
Daryl DeGrange
|
|
|
Left information on recorder about required final inspection
|
Conference | 9/24/2013 | 9/25/2013 | 9/25/2013 | A | DONE |
Daryl DeGrange
|
|
|
conference meeting on service change at 11:00AM Phone #: ###-#### >> Inspection requested via web by Kevin Koomler Discussed listed Meyers hubs,Bonding all metal surfaces within 5 ft of hot tub, panel directory
|
ELE-Aging Inspection | 9/2/2013 | 9/2/2013 | 9/3/2013 | | DONE |
Daryl DeGrange
|
|
|
Spoke with contractor, he said he would schedule an final inspection
|
Conference | 5/2/2013 | 5/2/2013 | 5/2/2013 | A | DONE |
Daryl DeGrange
|
|
|
Please call me on this Permit Phone #: ###-#### >> Inspection requested via web by Kevin Koomler Discussed service entrance raceway bonding for unfused conductors
|
Conference | 4/20/2012 | 4/20/2012 | 4/20/2012 | P | DONE |
Jack Frank
|
|
|
phone conference T&B hub not listed for grding and bonding NEC 250.90,91,92, also shall correct violation of common neutrals asap
|
Final | 4/20/2012 | 4/20/2012 | 4/20/2012 | P | CANC |
Jack Frank
|
|
|
|
Change Status to I | | | 4/20/2012 | | |
|
|
|
4-20-12 per Jack F needs to be in the issue mode ///dld
|
Temporary Service | 4/10/2012 | 4/10/2012 | 4/10/2012 | P | PART |
Jack Frank
|
|
|
kevin Phone #: ###-#### see failed p/s for info t/s o/h rec. ok
|
Permanent Service | 4/10/2012 | 4/11/2012 | 4/10/2012 | A | FAIL |
Jack Frank
|
|
|
kevin Phone #: ###-#### see added t/s note needs myers hub listed to meet art 250 for grding and bonding, and needs to address all old wiring done without permit, and inspection,and in violation of current and past NEC requirements
|
Issue PAID IN FULL permit | | | 3/30/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/30/2012 | | DONE |
|
|
|
This permit was created on the web by Kevin Koomler
|