Permit Information
Permit NumberELE12-00651
StatusFinaled
Name FOUR STAR ELECTRIC INC
Site Address 5707 W LUBKIN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: service change to 200 amp
wire in hot tub
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection4/30/20144/30/20144/30/2014 DONE
DetailsRock A. Hudson
Finalled 1-29-14. I will close permit
Final4/30/20144/30/20144/30/2014PPASS
DetailsRock A. Hudson
Final ok 1-29-14 by Daryl Degrange
Final1/29/20141/29/20141/29/2014ADONE
DetailsDaryl DeGrange
Idaho Power will be there at 10:00am for shutdown.I''ll replace the bonding hub then and bond the gutter by the hot tub. Phone #: ###-#### >> Inspection requested via web by Kevin Koomler correction done, final ok
ELE-Aging Inspection1/2/20141/2/20141/7/2014 DONE
DetailsDaryl DeGrange
Left information on recorder about required final inspection
Conference9/24/20139/25/20139/25/2013ADONE
DetailsDaryl DeGrange
conference meeting on service change at 11:00AM Phone #: ###-#### >> Inspection requested via web by Kevin Koomler Discussed listed Meyers hubs,Bonding all metal surfaces within 5 ft of hot tub, panel directory
ELE-Aging Inspection9/2/20139/2/20139/3/2013 DONE
DetailsDaryl DeGrange
Spoke with contractor, he said he would schedule an final inspection
Conference5/2/20135/2/20135/2/2013ADONE
DetailsDaryl DeGrange
Please call me on this Permit Phone #: ###-#### >> Inspection requested via web by Kevin Koomler Discussed service entrance raceway bonding for unfused conductors
Conference4/20/20124/20/20124/20/2012PDONE
DetailsJack Frank
phone conference T&B hub not listed for grding and bonding NEC 250.90,91,92, also shall correct violation of common neutrals asap
Final4/20/20124/20/20124/20/2012PCANC
DetailsJack Frank
Change Status to I  4/20/2012  
4-20-12 per Jack F needs to be in the issue mode ///dld
Temporary Service4/10/20124/10/20124/10/2012PPART
DetailsJack Frank
kevin Phone #: ###-#### see failed p/s for info t/s o/h rec. ok
Permanent Service4/10/20124/11/20124/10/2012AFAIL
DetailsJack Frank
kevin Phone #: ###-#### see added t/s note needs myers hub listed to meet art 250 for grding and bonding, and needs to address all old wiring done without permit, and inspection,and in violation of current and past NEC requirements
Issue PAID IN FULL permit  3/30/2012 DONE
Payment received via Govolutions
Application received  3/30/2012 DONE
This permit was created on the web by Kevin Koomler