DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/8/20145/8/20145/8/2014PPASS
DetailsRock A. Hudson
Darlene Phone #: ###-#### Basement rough in ok cover
Final5/5/20145/6/20145/6/2014PCANC
DetailsBob Reichert
Darlene Phone #: ###-#### see ri
Electrical Rough-In5/6/20145/6/20145/6/2014PFAIL
DetailsBob Reichert
Darlene Phone #: ###-#### met owner, left correction notice, NEC 300.4(A)(C) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 334.30 nm cable shall be stapled within 12" of box or 314.17(C) 8" if more than 1 cable, 210.52(A) shall install receptacles within 6' of entry and 12' maximum between receptacles, BCC shall not install devices until ri complete so free length of conductor can be inspected
ELE-Aging Inspection4/8/20144/8/20144/8/2014 DONE
DetailsBob Reichert
still under construction
ELE-Aging Inspection1/7/20141/7/20141/14/2014 CANC
DetailsBob Reichert
ELE-Request for Extension10/8/201310/9/201310/9/2013APASS
DetailsBob Reichert
ok for extension
ELE-Aging Inspection7/29/20137/29/20137/29/2013 DONE
DetailsBob Reichert
still under construction
Extend Permit 180 days4/12/20134/12/20134/12/2013PPASS
DetailsBob Reichert
darlene - call prior to going Phone #: ###-#### talked to owner, ok extend permit
Final10/4/201210/5/201210/5/2012PFAIL
DetailsBob Reichert
Dave Phone #: ###-#### explained that devices not to be installed, outlet spacing, stapling, 6" free conductor length, shall use connector for ground wires in box, call for ri next time
Electrical Rough-In5/31/20125/31/20125/31/2012PCANC
DetailsBob Reichert
dave Phone #: ###-#### see p/s
Permanent Service5/31/20125/31/20125/31/2012PPASS
DetailsBob Reichert
dave Phone #: ###-#### p/s o/h rec ok
Conference4/12/20124/12/20124/12/2012PDONE
DetailsBob Reichert
Dave Atwood-Please call at least 30 mins prior to inspection Phone #: ###-#### talked about service, wiring rooms, call for inspection, watch clearances for service
Application received  4/12/2012  
Issue PAID IN FULL permit  4/12/2012 DONE
DetailsBarbara Stitt