Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE12-00802
StatusFinaled
Name POWER PLUS INC
Site Address 1055 N CURTIS RD
Project Name 
Customer Number1228
ePlanReviewNo
Description
Electrical Permit - Repair: St. Al''s, South Tower, Service Upgrades
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice5/19/20145/19/20145/20/2014 DONE
DetailsRock A. Hudson
This permit finaled on the web by Debby Pierce
Final5/19/20145/19/20145/19/2014PPASS
DetailsRock A. Hudson
Greg Critchfield is contact, ###-####. thank you Phone #: ###-#### >> Inspection requested via web by Debby Pierce This permit covers installation of new service and prep work to provide conduits and junction points for quick disconnect of old gear and quick reconnect to new. Future permit will cover the change over from old gear to new gear. Conference in 2012 electrician stated city gave permission to feed fire pump from normal and emergency power in rigid conduit with out fire barrier. For work done to this point Final ok
ELE-Aging Inspection3/18/20143/18/20143/19/2014 DONE
DetailsRock A. Hudson
Still under construction
ELE-Aging Inspection12/17/201312/17/201312/17/2013 DONE
DetailsDaryl DeGrange
still under construction
Electrical Rough-In9/17/20139/17/20139/17/2013PPART
DetailsDoug A Poedy
Service Inspection, Contact is Greg Critchfield. ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis. Looked at all new service gear.
ELE-Aging Inspection8/9/20138/9/20138/12/2013 DONE
DetailsDaryl DeGrange
job still under construction
Conference5/9/20135/13/20135/13/2013ADONE
DetailsDaryl DeGrange
Greg Critchfield is contact ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis Discussed requirements for conductor separation between life safety and critical branch conductors
Conference3/21/20133/25/20133/25/2013ADONE
DetailsDaryl DeGrange
Greg Critchfield is contact. ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis DIscussed service grear working space clearances, personal doors
Electrical Rough-In2/5/20132/6/20132/6/2013APASS
DetailsDaryl DeGrange
Greg Critchfield is contact on this job, ###-#### Phone #: ###-#### >> Inspection requested via web by Debby Ellis Rough-in ok Installation of new emergency standby equipment in basement
Conference12/19/201212/20/201212/20/2012ADONE
DetailsDaryl DeGrange
Greg Critchfield is contact. ###-#### Phone #: ###-#### >> Inspection requested via web by Debby Ellis Discussed with electircan requirements for working clearances for service gear.
Conference12/19/201212/19/201212/19/2012PCANC
DetailsDoug A Poedy
Greg Critchfield is contact. ###-#### Phone #: ###-#### >> Inspection requested via web by Debby Ellis. Rescheduled
Permanent Service11/8/201211/8/201211/8/2012PPASS
DetailsDaryl DeGrange
p/s u/g rec ok
Electrical Rough-In11/8/201211/8/201211/8/2012PPASS
DetailsDaryl DeGrange
service inspection, Greg Critchfield is contact, ###-#### Phone #: ###-#### >> Inspection requested via web by Debby Ellis rough-in ok service conductors
Electrical Rough-In10/17/201210/18/201210/18/2012APASS
DetailsDaryl DeGrange
Underground, call Greg Crithfield ###-####
(By trash compactor) Phone #: ###-#### >> Inspection requested via web by Debby Ellis rough-in ok cover underground service lateral conduits
Conference6/1/20126/1/20126/1/2012ADONE
DetailsJack Frank
conference with ele contr. St Al's rep, and engineers, fire pump wiring ok
Electrical Rough-In5/16/20125/17/20125/17/2012APART
DetailsJack Frank
greg critchfield, ###-####, underground inspection, central tower, 10am or 11am. if you can... Phone #: ###-#### >> Inspection requested via web by Debby Ellis ok from vault to vault
Conference5/10/20125/11/20125/11/2012ADONE
DetailsJack Frank
conference with Greg and Luke on fir pump and new power for it
Conference5/9/20125/10/20125/10/2012ADONE
DetailsJack Frank
Call Greg Critchfield ###-####, he is in basement of Central Tower. Phone #: ###-#### >> Inspection requested via web by Debby Ellis see scheduled request for 05-11-12
Conference5/9/20125/9/20125/9/2012PDONE
DetailsBob Reichert
CALL Greg Critchfield at ###-####, might be down in basement, thanks Phone #: ###-#### >> Inspection requested via web by Debby Ellis talked to contractor, told to call 315 for am conference
Issue PAID IN FULL permit  4/17/2012 DONE
Payment received via Govolutions
Owner Supplied Equipment  4/17/2012  
Application received  4/17/2012 DONE
This permit was created on the web by Debby Ellis