Case Summary (ELE) | | | 6/6/2012 | | DONE |
Christina Prado
|
|
|
|
Final | 6/1/2012 | 6/4/2012 | 6/4/2012 | A | PASS |
Daryl DeGrange
|
|
|
call Mike Wrhel Phone #: ###-#### >> Inspection requested via web by Michael Wrhel n final ok
|
Final | 5/24/2012 | 5/24/2012 | 5/24/2012 | P | FAIL |
Daryl DeGrange
|
|
|
dan please call 15 min before going out for access Phone #: ###-#### NEC 210.(8) (A)(6) All receptacle to serve kitchen counter top shall have GFCI protection
|
Final | 5/23/2012 | 5/24/2012 | 5/24/2012 | A | NH |
Jack Frank
|
|
|
>> Inspection requested via web by Michael Wrhel notice posted called left message
|
Final | 5/18/2012 | 5/18/2012 | 5/18/2012 | P | FAIL |
Daryl DeGrange
|
|
|
call mike fr access ###-#### >> Inspection requested via web by Michael Wrhel GFCI receptacle on kitchen counter top not functioning properly, and receptacle left of range indecates no grounding conductor connection NEC 210.8(A) (6) All receptacles installed to servethe countertop surfaces shall have GFCI protection
|
Electrical Rough-In | 5/17/2012 | 5/17/2012 | 5/17/2012 | P | NH |
Daryl DeGrange
|
|
|
Call for access -- Michael Phone #: ###-#### personal belongings inside house
|
Application received | | | 5/17/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/17/2012 | | DONE |
|
|
|
|