Final | 1/28/2013 | 1/28/2013 | 1/28/2013 | P | PASS |
Daryl DeGrange
|
|
|
Roger Phone #: ###-#### final ok
|
Electrical Rough-In | 10/2/2012 | 10/3/2012 | 10/3/2012 | A | PASS |
Daryl DeGrange
|
|
|
Roger Phone #: ###-#### corrections done rough-in ok cover
|
Electrical Rough-In | 9/27/2012 | 9/28/2012 | 9/28/2012 | A | FAIL |
Daryl DeGrange
|
|
|
Roger Phone #: ###-#### NEC 300.4(D) Maintain romex 1 1/4 from edge of framing members NEC 334.30 NM cable shall be stapled (supported) within 12 in. of device box, than every 4 1/2 feet there after
|
Conference | 6/8/2012 | 6/11/2012 | 6/11/2012 | A | PASS |
Daryl DeGrange
|
|
|
call when on way//Roger Phone #: ###-#### Discussed with home owner wiring requirements for detach storage building
|
Application received | | | 6/8/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/8/2012 | | DONE |
|
|
|
|