First Notice | 6/7/2013 | 6/7/2013 | 2/11/2014 | | DONE |
Daryl DeGrange
|
|
|
This permit finaled on the web by Deb Gooden
|
Print Statement | | | 10/10/2013 | | DONE |
|
|
|
|
Final | 6/6/2013 | 6/7/2013 | 6/7/2013 | P | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Freinwald Phone #: ###-#### >> Inspection requested via web by Deb Gooden final ok
|
Final | 4/26/2013 | 4/29/2013 | 4/29/2013 | A | PART |
Daryl DeGrange
|
|
|
Contact: Clay Freinwald Phone #: ###-#### >> Inspection requested via web by Deb Gooden temporary occupancy ok
|
Electrical Rough-In | 4/9/2013 | 4/10/2013 | 4/10/2013 | A | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Freinwald - ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover ceiling grid 1500,1600,1700, and control room
|
Electrical Rough-In | 3/13/2013 | 3/15/2013 | 3/15/2013 | P | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Freinwald - ceiling rough-in please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover ceiling grid as per highlighted in green and dated
|
Electrical Rough-In | 3/12/2013 | 3/12/2013 | 3/12/2013 | P | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Freinwald, ceiling rough-in inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover areas as per highlighted in blue and dated on plan
|
Electrical Rough-In | 1/25/2013 | 1/29/2013 | 1/29/2013 | A | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Freinwald Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok 2 rooms as highlighted and dated on plans
|
Electrical Rough-In | 10/9/2012 | 10/9/2012 | 10/9/2012 | P | PASS |
Daryl DeGrange
|
|
|
2ND FLOOR CONCRETE SLAB INSPECTION PLEASE Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok pour slab 2nd floor
|
Electrical Rough-In | 9/28/2012 | 9/28/2012 | 9/28/2012 | P | PASS |
Daryl DeGrange
|
|
|
Contact: Clat Freinwald. 2nd floor slab inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover conduits in 2nd floor slab
|
Electrical Rough-In | 8/24/2012 | 8/27/2012 | 8/27/2012 | A | FAIL |
Bob Reichert
|
|
|
NEC 352.26 there shall not be more than 360 degrees total bends between pull points
|
Electrical Rough-In | 8/13/2012 | 8/15/2012 | 8/15/2012 | A | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Frienwald - underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover heat cable two locations SW &SE corners concrete pour
|
Electrical Rough-In | 8/13/2012 | 8/14/2012 | 8/14/2012 | A | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Frienwald - underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb rough-in ok cover NW corner underground
|
Electrical Rough-In | 8/10/2012 | 8/13/2012 | 8/13/2012 | A | PASS |
Daryl DeGrange
|
|
|
Contact: Clay Frienwald underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover east half concrete slab
|
Electrical Rough-In | 8/7/2012 | 8/8/2012 | 8/8/2012 | A | PART |
Bob Reichert
|
|
|
Contact: Clay Frienwald, underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden u/g from transformer ok towards building only, will see rest out of building later
|
Issue PAID IN FULL permit | | | 6/13/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/13/2012 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|