Final | 10/9/2012 | 10/11/2012 | 10/11/2012 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by danny perrine corrections done final ok
|
Final | 10/7/2012 | 10/9/2012 | 10/9/2012 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by danny perrine called, left correction notice, NEC 210.52(C) shall provide receptacles in countertop such that no point is over 2' from receptacle, 210.52(A) shall provide convenience receptacle in wall space below countertop, 406.4(D) receptacle faces shall be flush with or project from faceplate
|
Permanent Service | 8/8/2012 | 8/8/2012 | 8/8/2012 | P | PASS |
Bob Reichert
|
|
|
Danny Phone #: ###-#### p/s u/g n ok, 5 meters req'd
|
Permanent Service | 7/31/2012 | 8/1/2012 | 8/1/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by danny perrine called, shall strap riser, locate 2nd ground rod, shall remove foreign piping over electrical gear, shall provide diagram for gas meter layout to show clearance for electrical
|
Electrical Rough-In | 7/19/2012 | 7/20/2012 | 7/20/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by danny perrine called, left message about clearance at service area and riser room, ri ok
|
Electrical Rough-In | 7/18/2012 | 7/19/2012 | 7/19/2012 | P | NR |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by danny perrine still working on, told to recall
|
Issue PAID IN FULL permit | | | 7/18/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/18/2012 | | DONE |
|
|
|
This permit was created on the web by danny perrine
|
First Notice | 10/11/2012 | 10/11/2012 | | | |
Daryl DeGrange
|
|
|
|