Permit Information
Permit NumberELE12-02318
StatusFinaled
Name GLENN ELECTRIC
Site Address 3772 E TIMBERSAW DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/28/201211/28/201211/28/2012PPASS
DetailsRock A. Hudson
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn Final ok
Final11/21/201211/23/201211/23/2012AFAIL
DetailsRock A. Hudson
code 10020 Phone #: ###-#### >> Inspection requested via web by Bob Glenn
-Panel cover removed and misc plates missing
-Miswire in hall in from garage
-AC disconnects need labelled 1-2
- 10-2 in panel for garage heater white conductor needs marked or painted other than white
Electrical Rough-In10/31/201210/31/201210/31/2012PPASS
DetailsRock A. Hudson
WARM FLOOR RE-INSPECTION Phone #: ###-#### >> Inspection requested via web by Bob Glenn Floor heat rough in ok cover
Final10/30/201210/31/201210/30/2012AFAIL
DetailsRock A. Hudson
WARM FLOOR INSPECTION FOR MASTER BATHROOM Phone #: ###-#### >> Inspection requested via web by Bob Glenn Manufacturers instructions- recess factory splice in subfloor, recess sensor end in subfloor, nail plate lower plate.
Rough-In Permanent Service9/25/20129/26/20129/26/2012APASS
DetailsDaryl DeGrange
TANKS, BILL Phone #: ###-#### >> Inspection requested via web by Bob Glenn rough-in p/s u/g n ok
Electrical Rough-In9/24/20129/25/20129/25/2012AFAIL
DetailsRock A. Hudson
THANK YOU , BILL Phone #: ###-#### >> Inspection requested via web by Bob Glenn Called NEC320.23A NMB with-in 6' of attic access shall be protected from physical damage. NEC 334-17 NMB running through framing member shall be protected from physical damage where bored hole that are not 1 1/4" back from face of stud.
NEC 334.30 Securing and supporting- NMB stapled on 2x4 studs shall be supported 1 1/4" back from stud face.
BCC- One shall provide safe work space. Hand railing upstairs.
Change electrical permit to include 2nd AC, hot tub, and 14 rooms
Issue PAID IN FULL permit  9/17/2012 DONE
Payment received via Govolutions
Application received  9/17/2012 DONE
This permit was created on the web by Bob Glenn