Final | 11/19/2012 | 11/20/2012 | 11/20/2012 | P | PASS |
Bob Reichert
|
|
|
Side door to garage is open for entry to garage. Door to house thru garage is open if needed Phone #: ###-#### >> Inspection requested via web by John McConnell called about tree, corrections made, ok final
|
Final | 11/7/2012 | 11/7/2012 | 11/8/2012 | P | FAIL |
Bob Reichert
|
|
|
We have proper key for entrance to the property Phone #: ###-#### >> Inspection requested via web by John McConnell talked wth installer, said response would be on-line, gave 447 phone number, NEC 110.26(A) shall provide work space about equipment,408.36(D) shall supply additional fastener for back fed devices, 230.66 shall use equipment marked as service equipment, 250.50 all grounding electrodes shall be bonded together to form grounding electrode system, 110.22 shall provide disconnect identification, 690.17 shall provide labelling terminals can be energized from other source, 230, shall group and label disconnects, 110 combiner shall be listed assembly
|
Final | 11/5/2012 | 11/6/2012 | 11/6/2012 | P | NH |
Bob Reichert
|
|
|
called, will set up time
|
Application received | | | 9/17/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/17/2012 | | DONE |
Tisha Gallop
|
|
|
|