Final | 11/19/2012 | 11/20/2012 | 11/20/2012 | P | PASS |
Daryl DeGrange
|
|
|
Owners name and phone number: Jim Fouch 208 853 5092 Phone #: ###-#### >> Inspection requested via web by John McConnel corrections done final okl
|
Final | 11/6/2012 | 11/7/2012 | 11/7/2012 | A | FAIL |
Daryl DeGrange
|
|
|
Would like to meet with Bob Reichert for re-inspection of this project 11/7/12 @ 10:00am will have line drawing of the solar array and electrical connections. Ryan King, the solar array installer with EvenGreen Technology will also be attending. Ryan King - 208 850 8965 Phone #: ###-#### >> Inspection requested via web by John McConnell Corrections not completed NEC 110.26(A)(1) Working space for service panels
|
Final | 11/5/2012 | 11/6/2012 | 11/6/2012 | P | CANC |
Bob Reichert
|
|
|
For entrance to the property please call Jim Fouch at 208 853 5092 Phone #: ###-#### >> Inspection requested via web by John McConnell called, NEC 240, shall mount panel such that breaker handles below 6'-7", NEC 408, complete panel schedule, NEC 250, tie building grounds together, NEC 110 provide work space, NEC 230, shall not have 2 services in building, told contractor to provide drawings and recall for conference or ri
|
Application received | | | 10/9/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/9/2012 | | DONE |
Tisha Gallop
|
|
|
|