Final | 1/21/2013 | 1/22/2013 | 1/22/2013 | A | PASS |
Rock A. Hudson
|
|
|
Please call Mike Johnson if any questions Phone #: ###-#### >> Inspection requested via web by brad williams Final ok
|
Final | 12/17/2012 | 12/18/2012 | 12/18/2012 | A | FAIL |
Rock A. Hudson
|
|
|
>> Inspection requested via web by brad williams 230.9(B)(C) Over head service conductors shall not attach with in 3' of window.
|
Permanent Service | 12/18/2012 | 12/18/2012 | 12/18/2012 | P | PASS |
Rock A. Hudson
|
|
|
>> Inspection requested via web by brad williams Can not final until power swing is at least 3 feet away from windows p/s o/h rec ok
|
Conference | 12/10/2012 | 12/11/2012 | 12/11/2012 | A | CANC |
Rock A. Hudson
|
|
|
Mike Johnson with Alloway elec would like to meet with Doug Pody. Mike''s cell ph ###-#### >> Inspection requested via web by joel smith Will call in for am 12-12-12
|
Final | 12/10/2012 | 12/10/2012 | 12/10/2012 | P | FAIL |
Bob Reichert
|
|
|
>> Inspection requested via web by joel smith left correction notice, NEC 110.22(A) shall identify disconnects, 408.4 shall provide circuit directory, 110.26 shall provide work space about equipment, 314.28A(2) shall provide correct size enclosure used for angle pulls and splices, 230 shall use service rated equipment
|
Issue PAID IN FULL permit | | | 10/17/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/17/2012 | | DONE |
|
|
|
This permit was created on the web by joel smith
|
First Notice | 1/22/2013 | 1/22/2013 | | | |
Rock A. Hudson
|
|
|
|