Final | 1/15/2013 | 1/15/2013 | 1/15/2013 | P | PASS |
Rock A. Hudson
|
|
|
call when on way//Clayton Phone #: ###-#### Final ok
|
Electrical Rough-In | 11/20/2012 | 11/20/2012 | 11/20/2012 | P | PASS |
Rock A. Hudson
|
|
|
Clayton - call for access Phone #: ###-#### Basement rough in ok cover
|
Electrical Rough-In | 11/19/2012 | 11/19/2012 | 11/19/2012 | P | FAIL |
Rock A. Hudson
|
|
|
clayton Phone #: ###-#### - call 30 mins prior to meet 314.16 Box fill- 2 outlets have 20.25 cu in in 18 cu in boxes. 210.52 Shall have receptical with in 6' of closet door. 314.25 In complete installations each box shall have covers. (cans)
|
Conference | 11/16/2012 | 11/16/2012 | 11/16/2012 | P | DONE |
Bob Reichert
|
|
|
call 1/2 hr before to meet//Clayton Phone #: ###-#### talked about wiring basement, when to call for inspection, reviewed outlet spacing, stapling, 1 1/4", free length conductor
|
Application received | | | 11/16/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/16/2012 | | DONE |
|
|
|
|