Permit Information
Permit NumberELE12-02982
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 1000 W MYRTLE ST
Project NameJUMP - BELOW GRADE PARKING
Customer Number2012-10
ePlanReviewNo
Description
Electrical Permit - New: Furnish and install wiring for parking garage underground.///furnish and install fixtures and wiring for garage//ALD 3-1-13
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Statement  4/16/2018 DONE
Final12/8/201612/8/201612/8/2016PPASS
DetailsRock A. Hudson
Contact Tom for final walkdown of the basement garage. Phone #: ###-#### Inspection requested via web by Tom Betty Below grade parking garage final ok
Final12/8/201612/8/201612/8/2016PPASS
DetailsRock A. Hudson
Below grade parking garage no damage to electrical from flood. Final ok
Electrical Rough-In11/22/201611/22/201611/22/2016PFAIL
DetailsRock A. Hudson
Garbage compactors and Container winch motors Disconnect Locations and Use of Cords in lieu of fixed wiring Article 400 EM stops Phone #: ###-#### Inspection requested via web by Tom Betty
400.8(2)- Flexible cord for the hydraulic control shall not be run thru floor of platform. Shall be protected from physical damage. Rest of winches, disconnecting means, wiring methods ok
Conference11/16/201611/16/201611/16/2016PDONE
DetailsRock A. Hudson
RE-INSPECTION late AM if possible Thanks Rock Phone #: ###-#### Inspection requested via web by Tom Betty
Discussed Annex building outdoor lighting. Wanted to know if temp occupancy ok with lights hung on unfinished walls and columns. All egress lighting once installed shall remain in place for an emergency situation. If lights can remain in place YES, if lights are removed for finish NO.
Need Fence or barrier to keep public away from heat trace for grease tank
Final11/16/201611/16/201611/16/2016APART
DetailsRock A. Hudson
RE-INSPECTION late AM if possible Thanks Rock Phone #: ###-#### Inspection requested via web by Tom Betty
Must have a barrier, fence or enclosure around 277 volt heat tape for grease tank.
Jump parking garage temp final ok
Final11/15/201611/15/201611/15/2016PFAIL
DetailsRock A. Hudson
Call Tom for final walk down of Garage. Phone #: ###-#### Inspection requested via web by Tom Betty
110.3- Some general purpose receptacle outlets not working due to damage from construction. 1 circuit showed open neutral.
300.4- Flex connector cover on transformer T-DPAMPH missing. Exposed wiring subfect to physical damage.
300.15(A)- LB covers shall remain accessible after installation. Main level LB fitting 1/2 covered in concrete.
426.11- Grease tank in parking garage wrapped with heat trace cable shall have a barrier to protect from physical damage.
ELE-Aging Inspection10/27/201610/27/201611/2/2016 PASS
DetailsRock A. Hudson
Still under construction
ELE-Aging Inspection7/28/20167/28/20167/28/2016 PASS
DetailsRock A. Hudson
Still under construction
Electrical Rough-In4/28/20164/29/20164/29/2016APASS
DetailsRex Boyles
Call Brandon Robinson for basement restroom rough in. Phone #: ###-#### Inspection requested via web by Tony Keen r/i ok valet bathroom will install access panels for j boxes
ELE-Aging Inspection4/6/20164/6/20164/7/2016 DONE
DetailsRex Boyles
still under construction
ELE-Aging Inspection1/6/20161/6/20161/6/2016 DONE
DetailsRex Boyles
still under construction
ELE-Aging Inspection10/7/201510/7/201510/8/2015 DONE
DetailsRex Boyles
Still in progress
Final7/8/20157/10/20157/10/2015PPART
DetailsRex Boyles
Contact Mark Preston for generator vault inspection. Phone #: ###-#### Inspection requested via web by Tom Betty final ok on generator vault. Heat tape and battery chargers still need to be seen.
ELE-Aging Inspection4/17/20154/17/20154/17/2015 DONE
DetailsDaryl DeGrange
still under construction
ELE-Aging Inspection1/16/20151/16/20151/20/2015 DONE
DetailsRex Boyles
still under const.
Permanent Service10/17/201410/17/201410/17/2014PPASS
DetailsRex Boyles
Come to Lea Electric job trailer for breaker testing documentation. Phone #: ###-#### Inspection requested via web by Tom Betty p/s u/g n ok received performance test docs from switchgear manufacturer as per 230.95(C)
Permanent Service10/15/201410/15/201410/15/2014AFAIL
DetailsRex Boyles
Call Jon. This inspection is in conjunction with inspection for permit # ELE13-01291 Phone #: ###-#### Inspection requested via web by Tom Betty performance testing documents needed as per 230.95C prior to energizing
ELE-Aging Inspection8/25/20148/25/20148/28/2014 DONE
DetailsRex Boyles
still under construction
Electrical Rough-In10/22/201310/22/201310/22/2013PPASS
DetailsRock A. Hudson
Basement electrical room conduit under raised floors. Phone #: ###-#### >> Inspection requested via web by Tony Keen Garage basement 3 raised floor pours rough in ok cover
Electrical Rough-In8/21/20138/22/20138/22/2013APASS
DetailsRock A. Hudson
john Phone #: ###-#### Helix 3rd floor pour and garage north central as marked on print. Rough in ok cover
Electrical Rough-In8/8/20138/8/20138/8/2013PPASS
DetailsRock A. Hudson
tony Phone #: ###-#### Pour 14-B as noted on print. Rough in ok cover
Electrical Rough-In7/11/20137/12/20137/11/2013APASS
DetailsRock A. Hudson
Tony Phone #: ###-#### Basement ceiling pour north east of helix as noted on print rough in ok cover
Conference6/25/20136/25/20136/25/2013PDONE
DetailsRock A. Hudson
tony Phone #: ###-#### Discussed fire pump feeders and circuit conduits and fire protection and seperation from normal power conduits.
Electrical Rough-In6/21/20136/21/20136/21/2013PPASS
DetailsRock A. Hudson
John Phone #: ###-#### As noted on print 3rd floor, area B, PT deck Rough in ok cover
Electrical Rough-In6/17/20136/18/20136/18/2013PPASS
DetailsRock A. Hudson
John Novak Phone #: ###-#### Basement floor ceiling pour as noted on print rough in ok cover
Conference6/12/20136/13/20136/13/2013ADONE
DetailsRock A. Hudson
tony Phone #: ###-#### Discussed electrical for fire pumps that have moved from basement to 1st floor
Electrical Rough-In6/5/20136/5/20136/5/2013PPASS
DetailsRock A. Hudson
John Phone #: ###-#### Parking garage ceiling pour as noted on print rough in ok cover
Electrical Rough-In5/29/20135/30/20135/30/2013APASS
DetailsRock A. Hudson
Tony Phone #: ###-#### Ceiling pour noted on print rough in ok cover
Electrical Rough-In5/20/20135/20/20135/20/2013PPART
DetailsDoug A Poedy
John Phone #: ###-####. Underground section north of elevator 1 ok to cover.
Electrical Rough-In5/14/20135/14/20135/14/2013PPASS
DetailsRock A. Hudson
Tony Phone #: ###-#### Furthest south west ceiling pour rough in ok cover
Electrical Rough-In5/2/20135/2/20135/2/2013PPASS
DetailsRock A. Hudson
tony Phone #: ###-#### Parking garage ceiling pour as noted on print. Rough in ok cover
Electrical Rough-In4/23/20134/24/20134/24/2013PPASS
DetailsRock A. Hudson
Tony Phone #: ###-#### Parking garage ceiling pour as noted on print. Rough in ok cover
Electrical Rough-In4/11/20134/12/20134/12/2013PPASS
DetailsRock A. Hudson
Tony Phone #: ###-#### Parking garage ceiling pour marked on print. rough in ok cover
Electrical Rough-In4/3/20134/4/20134/4/2013PPASS
DetailsRock A. Hudson
tony Phone #: ###-#### Parking garage ceiling pour marked on print. Rough in ok cover
Conference4/1/20134/2/20134/2/2013ADONE
DetailsRock A. Hudson
Tony Phone #: ###-#### Discussed different manufactures service gear being intergrated together and the UL listing required showing products were tested as compatible.
Electrical Rough-In3/28/20133/29/20133/29/2013PPASS
DetailsRock A. Hudson
Tony Phone #: ###-#### South central parking garage ceiling pour. Rough in ok cover
Electrical Rough-In3/21/20133/22/20133/22/2013PPASS
DetailsRock A. Hudson
tony Phone #: ###-#### South central parking garage ceiling pour rough in ok cover
Issue PAID IN FULL permit  3/1/2013 DONE
Payment received via Govolutions
Electrical Rough-In2/19/20132/20/20132/20/2013APASS
DetailsRock A. Hudson
Tony Phone #: ###-#### Parking garage east central pour rough in ok cover
Electrical Rough-In2/8/20132/8/20132/8/2013PPASS
DetailsRock A. Hudson
Tony Phone #: ###-#### Parking garage N.E. corner ceiling marked on print rough in ok cover
Conference2/5/20132/6/20132/7/2013ADONE
DetailsRock A. Hudson
Tony King Phone #: ###-#### Discussed fire protection of generator feed to fire pump and how conduits are prerun. To be installed separate from normal power conduits and identified in red and signage as per code.
Conference1/29/20131/30/20131/30/2013ADONE
DetailsRock A. Hudson
Tony Phone #: ###-#### Discussed code requirements for fire pump feeds.
Conference12/17/201212/18/201212/18/2012ADONE
DetailsRock A. Hudson
LONNY Phone #: ###-#### Discussed additional ground rods to be added to ensure adequate true ground because of moisture barrier under entire project. sources of ground are ground rods, ground ring as drawn, concrete encased, metal water supply, fire sprinkler supply, building steel.
Issue PAID IN FULL permit  12/10/2012 DONE
Payment received via Govolutions
Application received  12/10/2012 DONE
This permit was created on the web by Vicki Moore
First Notice12/8/201612/8/2016   
DetailsRock A. Hudson
First Notice12/8/201612/8/2016   
DetailsRock A. Hudson