Case Summary (ELE) | | | 12/21/2012 | | DONE |
|
|
|
|
Electrical Rough-In | 12/13/2012 | 12/14/2012 | 12/14/2012 | A | PASS |
Rock A. Hudson
|
|
|
Please let me know if there are any issues. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Rough in ok
|
Final | 12/14/2012 | 12/14/2012 | 12/14/2012 | P | PASS |
Rock A. Hudson
|
|
|
Please let me know if there are any issues. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
|
Electrical Rough-In | 12/11/2012 | 12/12/2012 | 12/12/2012 | A | FAIL |
Rock A. Hudson
|
|
|
Added a light in the attic space. Attic is accessable from the outside gable. If everything is good please final. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan 230.27 Overhead conductors shall be attached by approved means. 230.24(B) Overhead conductors shall have 10' clearance over residectial property and 12' over residential driveway. 314.23(A) J-box to the right of service shall be secured. 300.10 Metal aceways shall be jopined together at all fittings. 300.11 All raceways and boxes shall be secured and supported.
|
Issue PAID IN FULL permit | | | 12/11/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/11/2012 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|