Final | 1/14/2013 | 1/14/2013 | 1/14/2013 | P | PASS |
Rock A. Hudson
|
|
|
MITCH Phone #: ###-#### Final ok
|
Permanent Service | 1/9/2013 | 1/9/2013 | 1/9/2013 | P | PASS |
Rock A. Hudson
|
|
|
Mitch Phone #: ###-#### p/s o/h rec ok
|
Electrical Rough-In | 1/4/2013 | 1/4/2013 | 1/4/2013 | P | PASS |
Rock A. Hudson
|
|
|
mitch Phone #: ###-#### Rough in ok cover
|
(F) Reprint permit | | | 12/19/2012 | | DONE |
|
|
|
|
Conference | 12/18/2012 | 12/18/2012 | 12/18/2012 | P | FAIL |
Rock A. Hudson
|
|
|
MITCH Phone #: ###-#### Work performed without permit. Service- NEC 230.70 A service disconnect shall be located where service entrance conducors enter building. Service grounding- NEC article 250. I can not verify the electrical service grounding and bonding. Interior of building has too many violations to list- a few are- open splices through out attic. Overcurrent devices not properly sized. Over current devices not list for panel. All light fixtures and exit signs shall be hung from a 2 hour fire rated box and be grounded
|
Application received | | | 12/17/2012 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/17/2012 | | DONE |
Tisha Gallop
|
|
|
|
First Notice | 1/14/2013 | 1/14/2013 | | | |
Rock A. Hudson
|
|
|
|