Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE12-03075
StatusFinaled
Name GLENNS ELECTRIC INC
Site Address 2635 E MESA VERDE CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/12/20138/12/20138/12/2013PPASS
DetailsRock A. Hudson
Corrections complete. Final ok
Final8/11/20138/12/20138/12/2013AFAIL
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Darrin Bybee called, shall add receptacle downstairs bedroom entry per NEC 210.52, shall label panels per NEC 408, pool lights shall be gfci protected, shall provide correct breakers in pool area panel
Conference6/10/20136/10/20136/10/2013ACANC
DetailsRock A. Hudson
2 upstairs bath floor heat Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Needed rough in insp.
Electrical Rough-In6/10/20136/10/20136/10/2013PPASS
DetailsRock A. Hudson
2 upstairs bath floor heat Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Master bath floor heat rough in ok cover
Conference6/7/20136/7/20136/7/2013ADONE
DetailsRock A. Hudson
Rock, need you to stop by and talk to owner and myself about exterior heat mat installation under pavers. Thanks. Darrin Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Discussed code requirements for snow melt mats under pavers
Conference5/13/20135/13/20135/13/2013PCANC
DetailsRock A. Hudson
floor heat in downstairs bathroom. Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Needed RI for floor heat basement
Electrical Rough-In5/13/20135/13/20135/13/2013PPASS
DetailsRock A. Hudson
floor heat in downstairs bathroom. Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Basement floor heat rough in ok cover
Rough-In Permanent Service2/8/20132/11/20132/11/2013APASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Rough in ok cover p/s u/g n ok
Rough-In Permanent Service1/31/20132/4/20132/4/2013APART
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Down furnace wall, service not finished, rough in ok cover
Conference1/14/20131/14/20131/14/2013PDONE
DetailsRock A. Hudson
Rock, stop by whenever, i will be on site all day.
Thanks
Darrin Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Discussed residential requirements for city of Boise
Electrical Rough-In1/14/20131/14/20131/14/2013PPASS
DetailsRock A. Hudson
Rock, stop by whenever, i will be on site all day.
Thanks
Darrin Phone #: ###-#### >> Inspection requested via web by Darrin Bybee Soffit rough in ok cover
Application received  12/18/2012  
Issue PAID IN FULL permit  12/18/2012 DONE