Final | 4/30/2013 | 5/1/2013 | 5/1/2013 | A | PASS |
Rock A. Hudson
|
|
|
The access code is 1607, thx! Phone #: ###-#### >> Inspection requested via web by Stephen Kren Final ok
|
Final | 4/25/2013 | 4/26/2013 | 4/26/2013 | A | FAIL |
Rock A. Hudson
|
|
|
The access code is 1608, any questions please call, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren 1-GFCI below panel shall have cover. 2- Remove old electrical in panel room. 3- Miss wire in kitchen GFCI. 4- Master bath light fixture hanging on wires, secure. 5- AC unit 25 a max, 30a breaker installed. 6- 1 circuit not labelled
|
Electrical Rough-In | 1/16/2013 | 1/17/2013 | 1/17/2013 | A | PASS |
Rock A. Hudson
|
|
|
The access code is 1607, please call for any questions, my cell is ###-####, thx! TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Rough in ok cover
|
Electrical Rough-In | 1/16/2013 | 1/16/2013 | 1/16/2013 | P | NH |
Rock A. Hudson
|
|
|
The access code is 1608, or the back door is unlocked, thanks, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Lock box code did not work
|
Permanent Service | 12/18/2012 | 12/19/2012 | 12/19/2012 | P | PASS |
Rock A. Hudson
|
|
|
We are doing a service upgrade starting Wed morning, we should be ready for a pm insp. we are trying to get an inspection so we can turn the power on the same day. Phone #: ###-#### >> Inspection requested via web by Stephen Kren p/s o/h rec ok
|
Issue PAID IN FULL permit | | | 12/18/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/18/2012 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|