First Notice | 3/21/2013 | 3/21/2013 | 5/18/2013 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Kurt Carlson
|
Final | 3/20/2013 | 3/21/2013 | 3/21/2013 | P | PASS |
Bob Reichert
|
|
|
Bill Phone #: ###-#### ok final
|
Permanent Service | 2/13/2013 | 2/15/2013 | 2/15/2013 | A | PASS |
Bob Reichert
|
|
|
Main service, multi meter pack. The AIC calcs from IPCO Are: Line to Line= 9,653. The Line to neutral calc is 6,840. Myers hubs have been installed, water in building is poly pipe, 2 ground rods to service. Bill Litzebauer can meet on site. Phone #: ###-#### >> Inspection requested via web by Kurt Carlson p/s u/g n ok (meter pak)
|
Rough-In Permanent Service | 2/12/2013 | 2/12/2013 | 2/12/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kurt Carlson Service entrance conduits entering from top of service grear shall enter through listed meyers hub
|
Issue PAID IN FULL permit | | | 1/14/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/14/2013 | | DONE |
|
|
|
This permit was created on the web by Kurt Carlson
|