First Notice | 1/31/2013 | 1/31/2013 | 1/23/2017 | | DONE |
Daryl DeGrange
|
|
|
This permit finaled on the web by Mike Swift
|
Final | 1/30/2013 | 1/31/2013 | 1/31/2013 | A | PASS |
Daryl DeGrange
|
|
|
After 9:00 please-Virgil Phone #: ###-#### corrections done final ok
|
Final | 1/28/2013 | 1/29/2013 | 1/29/2013 | A | FAIL |
Daryl DeGrange
|
|
|
After 9 AM - Virgil Phone #: ###-#### NEC 358.30 Shall secure EMT within 3 ft of termination point. NEC 511.12 All 15 and 20 ampere 120 volt recepectacles installed in commerial garages shall have GFCI protection NEC 408.4 need to label panel directory
|
Electrical Rough-In | 1/23/2013 | 1/23/2013 | 1/23/2013 | P | PASS |
Daryl DeGrange
|
|
|
late pm please//Virgil Phone #: ###-#### rough-in ok cover under ground with at least 2 in. of concrete
|
Issue PAID IN FULL permit | | | 1/22/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 1/22/2013 | | |
|
|
|
|
Application received | | | 1/22/2013 | | DONE |
|
|
|
This permit was created on the web by Mike Swift
|