Final | 6/11/2013 | 6/12/2013 | 6/12/2013 | A | PASS |
Rock A. Hudson
|
|
|
Key Code on back porch 3636 Phone #: ###-#### >> Inspection requested via web by cal crosby Final ok
|
Final | 6/10/2013 | 6/10/2013 | 6/10/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Key Code 3636 Phone #: ###-#### >> Inspection requested via web by cal crosby 408.4- Circuit directory- Label garage circuit in meter main. 110.22(A)- Identification of disconnecting means- identify garage disconnect switch and ac disconnects. 440.12(A)- Overcurrent device shall be sized to the name plate rating. 20a on a 15a max ac. 342.30(A)- Service mast shall be secured with in 3' of meter base. Wrong number given on ispection request.
|
Fees Due Hold | 2/14/2013 | | 2/14/2013 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 2/14/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Electrical Rough-In | 2/12/2013 | 2/12/2013 | 2/12/2013 | P | PASS |
Rock A. Hudson
|
|
|
CAL Phone #: ###-#### Full remodel rough in ok cover
|
Permanent Service | 2/5/2013 | 2/6/2013 | 2/6/2013 | P | PASS |
Rock A. Hudson
|
|
|
Cal Phone #: ###-#### >> Inspection requested via web by cal crosby p/s o/h rec ok
|
Issue PAID IN FULL permit | | | 2/5/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/5/2013 | | DONE |
|
|
|
This permit was created on the web by cal crosby
|