Permanent Service | 2/11/2013 | 2/12/2013 | 2/12/2013 | P | PASS |
Rock A. Hudson
|
|
|
Service repairs as per Rock. Phone #: ###-#### >> Inspection requested via web by Greg Idsinga p/s o/h rec ok
|
Final | 2/12/2013 | 2/12/2013 | 2/12/2013 | P | PASS |
Rock A. Hudson
|
|
|
Service repairs as per Rock. Phone #: ###-#### >> Inspection requested via web by Greg Idsinga p/s o/h rec ok Final ok
|
Permanent Service | 2/7/2013 | 2/8/2013 | 2/8/2013 | A | PART |
Rock A. Hudson
|
|
|
I will call when we are ready for the service to be energized. Thank you Phone #: ###-#### >> Inspection requested via web by Greg Idsinga Temporary hook up only. Unfused conductors enter building and terminate at panel locations that we do not have access to. BCC Section 4-05-32 Code violation shall not be retained. The existing wiring shall be in accordance with present code. BCC Section 4-05-31C Unfused conductors when inside a building or structure shall be install in a receway for underground services only. NEC 230.70 Means shall be provided to disconnect all conductors in a building from the service entrance conductors. t/s o/h rec ok
|
Issue PAID IN FULL permit | | | 2/7/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/7/2013 | | DONE |
|
|
|
This permit was created on the web by Greg Idsinga
|