Final | 4/16/2013 | 4/16/2013 | 4/16/2013 | A | PASS |
Bob Reichert
|
|
|
Office Contact: Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe ok final
|
Rough-In Permanent Service | 3/20/2013 | 3/21/2013 | 3/21/2013 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/18/2013 | 3/19/2013 | 3/19/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called, left correction notice, NEC 314.17(C) nm cable shall be stapled within 8" of box, 300.4(A)(1) shall add nailplates if edge of bored hole is less than 1 1/4" from face of framing member, 210.52 shall add receptacle in wall over 2', BCC shall add box for bath light, shall not cover any wiring prior to inspection- foam in holes
|
Issue PAID IN FULL permit | | | 3/18/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/18/2013 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|