Final | 6/17/2013 | 6/17/2013 | 6/17/2013 | P | PASS |
Daryl DeGrange
|
|
|
call 20 min before to meet//Alan Phone #: ###-#### final ok
|
Final | 6/11/2013 | 6/11/2013 | 6/11/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Alan-Please call at least 30 mins prior to inspection Phone #: ###-#### Not all corrections completed, all 15 and 20 ampere 120 volt receptacles in garage and receptacles serving kitchen counter shall have GFCI protection.
|
Final | 4/25/2013 | 4/25/2013 | 4/25/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Please call 40min prior for access - alan Phone #: ###-#### Receptacles that require GFCI protection NEC 210.8(2) garage NEC 210.8(6) kitchens NEC 408.11 Tamper resistant receptacles in dwelling units
|
Electrical Rough-In | 4/11/2013 | 4/11/2013 | 4/11/2013 | A | PASS |
Daryl DeGrange
|
|
|
rough-in ok cover
|
Conference | 4/10/2013 | 4/11/2013 | 4/11/2013 | A | DONE |
Daryl DeGrange
|
|
|
alan Phone #: ###-####
|
Application received | | | 4/10/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/10/2013 | | DONE |
|
|
|
|