ELE-Aging Inspection | 4/27/2015 | 4/27/2015 | 4/27/2015 | | DONE |
Rock A. Hudson
|
|
|
Permit search showed permit that covered corrections
|
Final | 4/27/2015 | 4/27/2015 | 4/27/2015 | P | PASS |
Rock A. Hudson
|
|
|
Permit ELE13-00919 covers corrections. Final ok
|
Permanent Service | 4/12/2013 | 4/12/2013 | 4/12/2013 | P | FAIL |
Daryl DeGrange
|
|
|
josef - call 30 mins prior to meet Phone #: ###-#### NEC 250.53(G) Ground rod shall be at least 8 ft. in contact with soil, second eight foot grounding electrode six feet apart connected with #6 copper conductor. NEC 250.52 grounding conductor to metal underground water pipe,attach within 5 ft. from the point of entrance to the building. Plug open knock out in back of panel.Install breaker in open space in panel or blank off Explained to property owner that he would be required to hire an Idaho licence electrical contractor to do the electrical corrections on the rental property.
|
Application received | | | 4/12/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/12/2013 | | DONE |
|
|
|
|