Electrical Permit - New: New electrical
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/27/20142/28/20142/28/2014APASS
DetailsRex Boyles
Correction have been made. Please call Bill ahead for entry. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast final ok
Final2/20/20142/21/20142/21/2014AFAIL
DetailsRock A. Hudson
Please call Bill ahead for entry. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast 314.20 Outside lights, if boxes are recessed more than 1/4" plaster ring shall be installed. 314.23 non mettalic boxes shall be securily mounted (oven). 230.77-service disconnect shall be legibly identified.
Rough-In Permanent Service9/11/20139/12/20139/12/2013APASS
DetailsDaryl DeGrange
This is a reinspection Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Corrections done rough-in p/s u/g n ok main house and detach garage
Rough-In Permanent Service9/9/20139/10/20139/10/2013AFAIL
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast
300.4 NM cable shall be protected from physical damage up front bed, up back bed, entry and office and pantry.
250 Metal piping system shall be bonded if 10' or more continuous copper.
Electrical Rough-In6/12/20136/12/20136/12/2013PPASS
DetailsBob Reichert
Please inspect trench in ground. If you have any questions call Bill @ ###-####. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast u/g house to garage ok cover
Issue PAID IN FULL permit  6/12/2013 DONE
Payment received via Govolutions
Application received  6/12/2013 DONE
This permit was created on the web by Rhonda Yoast