Final | 3/23/2015 | 3/23/2015 | 3/23/2015 | P | PASS |
Rock A. Hudson
|
|
|
Early afternoon please - Eric Phone #: ###-#### Final ok
|
Final | 9/19/2014 | 9/26/2014 | 9/26/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Eric Phone #: ###-#### 424.39- Receptical outlet shall not be located over baseboard heater. 408.4 complete circuit directory. Disconnecting means for water heater
|
Electrical Rough-In | 1/21/2014 | 1/22/2014 | 1/22/2014 | P | PASS |
Daryl DeGrange
|
|
|
eric Phone #: ###-#### corrections done, rough-in ok cover
|
Electrical Rough-In | 1/16/2014 | 1/17/2014 | 1/17/2014 | P | FAIL |
Bob Reichert
|
|
|
requests 1pm - eric Phone #: ###-#### shall add 2 receptacles upstairs, trim jacket in boxes, add ko seals in panel, add abrasion protection for can lights, verify 6" free conductor length for grounds in boxes
|
Rough-In Permanent Service | 1/13/2014 | 1/14/2014 | 1/14/2014 | P | NR |
Daryl DeGrange
|
|
|
Eric Phone #: ###-#### Not ready for cover, turned into conference
|
Permanent Service | 1/14/2014 | 1/14/2014 | 1/14/2014 | P | PASS |
Daryl DeGrange
|
|
|
Eric Phone #: ###-#### p/s o/h n ok
|
Conference | 11/19/2013 | 11/20/2013 | 11/21/2013 | P | DONE |
Bob Reichert
|
|
|
Eric Phone #: ###-#### talked about wiring garage, office, when to call for inspection
|
Application received | | | 6/14/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/14/2013 | | DONE |
|
|
|
|