Final | 6/27/2013 | 6/27/2013 | 6/27/2013 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Randy Fletcher final ok
|
Permanent Service | 6/19/2013 | 6/19/2013 | 6/19/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Final on Service Phone #: ###-#### >> Inspection requested via web by Randy Fletcher NEC 110.26 Dedicated equipment space vent pipe under panel. stall indentify current carrying conductors NEC 408.4 circuit directory to brief
|
Rough-In Permanent Service | 6/18/2013 | 6/18/2013 | 6/18/2013 | P | PASS |
Bob Reichert
|
|
|
need ok for Idaho Power to reconnect Phone #: ###-#### >> Inspection requested via web by Randy Fletcher met electrician, check at final that pvc vent moved from under panel, that clearance over garage to west is met, see if branch circuit wiring ok, p/s o/h rec ok
|
Issue PAID IN FULL permit | | | 6/18/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/18/2013 | | DONE |
|
|
|
This permit was created on the web by Randy Fletcher
|