Final | 10/1/2013 | 10/1/2013 | 10/1/2013 | A | PASS |
Bob Reichert
|
|
|
code is 7530. Thanks! Phone #: ###-#### >> Inspection requested via web by Darryn Coburn corrections made, ok final
|
Final | 9/20/2013 | 9/20/2013 | 9/20/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, shall add access plate for gec, add outlets for countertops and convenience receptacles
|
Rough-In Permanent Service | 6/24/2013 | 6/24/2013 | 6/24/2013 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn see duplicate request
|
Rough-In Permanent Service | 6/24/2013 | 6/24/2013 | 6/24/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
|
Issue PAID IN FULL permit | | | 6/20/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/20/2013 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|