DOC - Permit Expired | 2/1/2019 | 2/1/2019 | 2/1/2019 | A | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
ELE-Aging Inspection | 11/30/2018 | 11/30/2018 | 12/3/2018 | | DONE |
Mark Moncarr
|
|
|
Please call with update on job being done.
|
ELE-Aging Inspection | 8/31/2018 | 8/31/2018 | 8/31/2018 | | DONE |
Mark Moncarr
|
|
|
Schedule a final inspection.
|
ELE-Aging Inspection | 6/1/2018 | 6/1/2018 | 6/4/2018 | | DONE |
Mark Moncarr
|
|
|
Please schedule for a final inspection.
|
ELE-Aging Inspection | 3/2/2018 | 3/2/2018 | 3/2/2018 | | DONE |
Mark Moncarr
|
|
|
Please schedule for a final inspection.
|
ELE-Aging Inspection | 12/1/2017 | 12/1/2017 | 12/1/2017 | | DONE |
Mark Moncarr
|
|
|
Please call with progress on work.
|
ELE-Aging Inspection | 8/31/2017 | 8/31/2017 | 8/31/2017 | | FAIL |
Mark Moncarr
|
|
|
No inspection requested at this time.
|
ELE-Aging Inspection | 6/1/2017 | 6/1/2017 | 6/1/2017 | | DONE |
Mark Moncarr
|
|
|
Inspector has talked to homeowner via phone, and also left a message on another occasion. No inspection requested at this time.
|
ELE-Aging Inspection | 2/20/2017 | 2/20/2017 | 2/21/2017 | | DONE |
Mark Moncarr
|
|
|
Message was left by inspector on 1/5/16. No inspection requested at this time.
|
ELE-Aging Inspection | 7/6/2016 | 7/6/2016 | 7/13/2016 | | CANC |
Eric Story
|
|
|
too busy
|
ELE-Aging Inspection | 4/5/2016 | 4/5/2016 | 4/5/2016 | | CANC |
Eric Story
|
|
|
too busy
|
ELE-Aging Inspection | 1/5/2016 | 1/5/2016 | 1/5/2016 | | DONE |
Eric Story
|
|
|
called and left a message
|
ELE-Aging Inspection | 9/22/2015 | 9/22/2015 | 9/22/2015 | | DONE |
Eric Story
|
|
|
talk with don he said he would be in touch to finish the home soon
|
Permanent Service | 10/7/2013 | 10/8/2013 | 10/8/2013 | A | PASS |
Rock A. Hudson
|
|
|
don Phone #: ###-#### p/s o/h n ok
|
Permanent Service | 9/26/2013 | 9/27/2013 | 9/27/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Robert Foster Phone #: ###-#### Grounding electode conductor shall not be ran through meter. 250.24- Grounding electode conductor shall terminate at the same bus bar as grounded conductor. 250.26- Main bonding jumper shall be installed. 334.30- NM cable shall be secured with in 8" of boxes.
|
Electrical Rough-In | 7/2/2013 | 7/3/2013 | 7/3/2013 | A | NR |
Rock A. Hudson
|
|
|
don Phone #: ###-#### Service grounding and feeders not in, recepticals 18" minimum to bottom of boxes, NM support within 12" of junction boxes anddevice boxes.
|
Conference | 7/2/2013 | 7/3/2013 | 7/3/2013 | A | DONE |
Rock A. Hudson
|
|
|
don Phone #: ###-#### Discussed receptical height in garage, NM support, service grounding and feeders, and owner would like to partial final garage when ready.
|
Application received | | | 6/24/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/24/2013 | | DONE |
|
|
|
|