Final | 9/25/2013 | 9/25/2013 | 9/25/2013 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn ok final
|
Rough-In Permanent Service | 7/17/2013 | 7/18/2013 | 7/18/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 7/17/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/17/2013 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|