First Notice | 12/12/2013 | 12/12/2013 | 1/16/2014 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Thomas Jenkins
|
Final | 12/11/2013 | 12/12/2013 | 12/12/2013 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins corrections made, ok final, no card found to sign
|
Final | 12/9/2013 | 12/10/2013 | 12/10/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins called, left correction notice, NEC 110.26(A) shall provide work space for transformer, 400.8 shall not use flexible cord or cable as a substitute for fixed wiring
|
Final | 11/21/2013 | 11/21/2013 | 11/21/2013 | P | PART |
Bob Reichert
|
|
|
partial final for occupancy. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins corrections made, t/o ok, will sign card at final, after all pool equipment installed
|
Final | 11/20/2013 | 11/20/2013 | 11/21/2013 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins called, outdoor receptacles shall be wr type per NEC 406.8, shall close openings in box in wall, at final, need to part final until all pool equipment installed
|
Permanent Service | 11/12/2013 | 11/13/2013 | 11/13/2013 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins corrections made, p/s u/g n ok
|
Permanent Service | 11/12/2013 | 11/12/2013 | 11/12/2013 | P | FAIL |
Rock A. Hudson
|
|
|
tom Phone #: ###-#### 250.24- Grounding electrode conductor shall terminate at the same busbar or terminal as grounded conductor. 310.15(B)- 400 amp service shall be fed with parallel 3/0 or equivalent single condutors. 310.15(C)- Provide calculation to prove wingle conductor 3/0 conductors adequate.
|
Change Status to I | | | 11/12/2013 | | |
|
|
|
inspector finaled in error
|
Electrical Rough-In | 11/5/2013 | 11/5/2013 | 11/5/2013 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Locker and bath rooms ceiling rough in ok cover
|
Final | 11/5/2013 | 11/5/2013 | 11/5/2013 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Service final ok
|
Electrical Rough-In | 10/16/2013 | 10/16/2013 | 10/16/2013 | P | PASS |
Bob Reichert
|
|
|
Walls in post office Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins ok cover post office walls, ceiling
|
Electrical Rough-In | 8/28/2013 | 8/28/2013 | 8/28/2013 | P | PASS |
Daryl DeGrange
|
|
|
Ruffin of boxes in concrete walls Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins rough-in ok cover
|
Electrical Rough-In | 8/27/2013 | 8/28/2013 | 8/28/2013 | A | NR |
Bob Reichert
|
|
|
rough in of masonry boxes in concrete walls. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins called, left message
|
Electrical Rough-In | 7/29/2013 | 7/29/2013 | 7/29/2013 | P | PASS |
Bob Reichert
|
|
|
Inspection for uffer. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins ok pour concrete encased electrode
|
Issue PAID IN FULL permit | | | 7/29/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/29/2013 | | DONE |
|
|
|
This permit was created on the web by Thomas Jenkins
|