Final | 9/11/2014 | 9/12/2014 | 9/12/2014 | A | PASS |
Bob Reichert
|
|
|
Martin Phone #: ###-#### corrections made, ok final
|
Final | 7/30/2014 | 7/30/2014 | 7/30/2014 | P | FAIL |
Bob Reichert
|
|
|
Martin Phone #: ###-#### met owner left correction notice, NEC 408.4 shall provide clear and concise circuit directory, 406.8(B) shall install weather resistant receptacles outside, 406.11 shall use tamper resistant receptacles, 406.8(A) shall install in-use covers outside, 210.8(A)(2) shall install gfci receptacles, 352.30(A) shall strap pvc within 3' of termination, 404.4 shall install weather resistant covers for switches, 406 shall provide arc fault protection for bedroom, checked up bedroom, owner moved in, couldn't check all outlets
|
Final | 7/29/2014 | 7/29/2014 | 7/29/2014 | P | NR |
Bob Reichert
|
|
|
Martin Phone #: ###-#### called, told owner to provide panel schedule, receptacles shall be gfci protected, provide in-use covers, install w/p switch covers, strap risers, outside receptacles shall be weather resistant
|
Electrical Rough-In | 9/30/2013 | 10/1/2013 | 10/1/2013 | A | PASS |
Bob Reichert
|
|
|
Martin Phone #: ###-#### called, left message, ri ok
|
Electrical Rough-In | 9/30/2013 | 9/30/2013 | 9/30/2013 | P | FAIL |
Bob Reichert
|
|
|
Martin Phone #: ###-#### called, left correction notice, NEC 334.30 shalll support nm cable within 12" of box, 300.4(A)(D) shall provide protection for cable if 1 1/4" from edge of framing member not kept, 250.68 shall provide access for gec, 110.12 shall not use damaged parts, BCC shall add rooms to permit, 4
|
(F) Reprint permit | | | 9/30/2013 | | DONE |
Barbara Stitt
|
|
|
|
Electrical Rough-In | 8/12/2013 | 8/12/2013 | 8/12/2013 | P | FAIL |
Bob Reichert
|
|
|
martin Phone #: ###-#### called, no answer, left correction notice, shall staple nm within 8" of box, shall provide nailplates, shall provide 1 1/4" protection of nm cable on studs, shall staple staple nm cable out of panel
|
Conference | 7/29/2013 | 7/31/2013 | 7/31/2013 | A | DONE |
Bob Reichert
|
|
|
martin Phone #: ###-#### talked about wiring garage
|
Application received | | | 7/29/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/29/2013 | | DONE |
|
|
|
|