Final | 10/17/2013 | 10/18/2013 | 10/18/2013 | A | PASS |
Rock A. Hudson
|
|
|
It will be open. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
|
Final | 10/16/2013 | 10/17/2013 | 10/17/2013 | A | FAIL |
Rock A. Hudson
|
|
|
It will be unlocked. let me know if there are any problems. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan 410.16- Incandescent light fixture located in closet shall have 12" clearance from shelf. 440.14 - A disconnecting means shall be provided with in sight of AC unit. 210.8- All 15 and 20 amp 120 volt recepticals located in garage shall have GFCI protection. 210.52(C)(3)- At least one receptical outlet shall be installed at peninsula counter top space. 342.30- Service riser shall be secured with in 3' of meter can.
|
Rough-In Permanent Service | 8/27/2013 | 8/28/2013 | 8/28/2013 | A | PASS |
Bob Reichert
|
|
|
Please let me know if there are any problems. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan corrections made, ri ok, p/s o/h n ok
|
Rough-In Permanent Service | 8/21/2013 | 8/22/2013 | 8/22/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Please let me know if there are any problems. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan 400.8 Flexible cords shall not be ran in wall or attics. exception- type TC cable is allowed if instaled in a raceway. 336.10 (2)
|
Rough-In Permanent Service | 8/20/2013 | 8/21/2013 | 8/21/2013 | P | CANC |
Rock A. Hudson
|
|
|
Please let me know if there are any issues. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Inspection cancelled from web by: Clay Morgan
|
Issue PAID IN FULL permit | | | 8/19/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/19/2013 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|