Final | 11/25/2013 | 11/26/2013 | 11/26/2013 | P | PASS |
Rock A. Hudson
|
|
|
Corrections have been made. Call either tim at listed number. Or john harvey at 9899410. House should be open Phone #: ###-#### >> Inspection requested via web by John Harvey Final ok
|
Final | 11/21/2013 | 11/22/2013 | 11/22/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Call general contractor to allow entrance into house Phone #: ###-#### >> Inspection requested via web by John Harvey 210.8- All 120 volt receptical outlets shall have GFCI protection. 110.3- 2 receptical outlets in family room do not work. 210.8- All bath receptical outlets shall have GFCI protection. 210.52- At least 1 receptical outlet shall be located with in 36" of basin and outside cabinet. 410.16 Luminaire located in closets shall have minimum of 6" clearence from shelf. 314.20- Boxes located in tile recessed more than 1/4" shall have box extenders installed. 408.4- Garage panel schedule shall be labelled.
|
Permanent Service | 10/24/2013 | 10/24/2013 | 10/24/2013 | P | PASS |
Rock A. Hudson
|
|
|
Swing from temp to permanent service. House is not ready.
John harvey will be point of contact Phone #: ###-#### >> Inspection requested via web by John Harvey p/s o/h n ok
|
Electrical Rough-In | 8/28/2013 | 8/28/2013 | 8/28/2013 | P | PASS |
Rock A. Hudson
|
|
|
General contactor (tim) is available by phone. Inspection can be done anytime Phone #: ###-#### >> Inspection requested via web by John Harvey House and garage rough in ok cover
|
Electrical Rough-In | 8/27/2013 | 8/27/2013 | 8/27/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Corrections made. Ufer access will be addressed with access panel after sheetrock is installed. Phone #: ###-#### >> Inspection requested via web by John Harvey Corections not complete, NM cable shall be secured at each light box or stub, cans and boxes. 14-2 pinched at the entry HVAC boot or basement ceiling.
|
Electrical Rough-In | 8/26/2013 | 8/27/2013 | 8/27/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Tim (General Contractor) is point of contact and is reachable by phone. John Harvey is out of town. Please call Tim with any issues. Thank you. Phone #: ###-#### >> Inspection requested via web by John Harvey NM cable shall be protected from physical damage above house panel. NM cable does not enter fireplace. Ufer or concrete encased electrode conndction shall be accessible. NM cable shall be secured at each box,
|
Issue PAID IN FULL permit | | | 8/20/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/20/2013 | | DONE |
|
|
|
This permit was created on the web by John Harvey
|