Final | 10/15/2013 | 10/16/2013 | 10/16/2013 | A | PASS |
Rock A. Hudson
|
|
|
jay Phone #: ###-#### Final ok
|
Final | 10/14/2013 | 10/15/2013 | 10/15/2013 | A | FAIL |
Bob Reichert
|
|
|
see 10/14/13
|
Final | 10/14/2013 | 10/14/2013 | 10/15/2013 | P | FAIL |
Bob Reichert
|
|
|
Jay ###-#### called, left correction notice, NEC 406 shall tighten receptacle, 210 shall not have porch receptacle on small appliance branch circuit, 334 shall secure nm cable within 12" of panel, 348 shall secure flex within 12" of termination
|
Rough-In Permanent Service | 8/28/2013 | 9/3/2013 | 9/3/2013 | P | PASS |
Rock A. Hudson
|
|
|
Call Jay ###-#### when approximately 1 hr away for access Phone #: ###-#### >> Inspection requested via web by Jay VanSchoiack Not all walls opened up. Most code required recepticals installed. Rough in ok cover p/s o/h rec ok
|
Issue PAID IN FULL permit | | | 8/28/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/28/2013 | | DONE |
|
|
|
This permit was created on the web by Jay VanSchoiack
|