First Notice | 1/13/2014 | 1/13/2014 | 1/17/2014 | | DONE |
Daryl DeGrange
|
|
|
This permit finaled on the web by Richard Montgomery
|
Final | 1/13/2014 | 1/13/2014 | 1/13/2014 | P | PASS |
Daryl DeGrange
|
|
|
Final for the new Western Aircraft warehouse. Contact is Nathan Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery final ok
|
Electrical Rough-In | 12/27/2013 | 12/30/2013 | 12/30/2013 | A | PASS |
Daryl DeGrange
|
|
|
Re-inspection of grid. Contact is Nathan Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery correction done, rough-in ok cover
|
Electrical Rough-In | 12/27/2013 | 12/27/2013 | 12/27/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Grid inspection. Contact is Nathan Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery NEC 314.28 (A)(1) Straight pull, the length of the box shall not be less eight times of the largest raceway, plus sum of diameter of all other entries. Support cabling off ceiling grid
|
Permanent Service | 12/23/2013 | 12/23/2013 | 12/23/2013 | P | PASS |
Daryl DeGrange
|
|
|
Service inspection for new Warehouse. Contact is Nate Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery p/s u/g n ok
|
Electrical Rough-In | 12/2/2013 | 12/2/2013 | 12/2/2013 | P | PASS |
Bob Reichert
|
|
|
Rough inspection of new interior wall in the warehouse area. Contact is Nathan Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery ok cover wall
|
Electrical Rough-In | 11/22/2013 | 11/25/2013 | 11/25/2013 | A | PASS |
Bob Reichert
|
|
|
Rough inspect of interior office walls. Contact is Nate Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery asked to check on address since posted 4308, ok cover interior walls only
|
Electrical Rough-In | 11/12/2013 | 11/12/2013 | 11/12/2013 | P | PASS |
Daryl DeGrange
|
|
|
Inspect for exterior warehouse walls. Contact on job is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover
|
Electrical Rough-In | 11/6/2013 | 11/7/2013 | 11/6/2013 | A | PASS |
Daryl DeGrange
|
|
|
Office Area outer walls rough inspection. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover
|
Electrical Rough-In | 10/3/2013 | 10/3/2013 | 10/3/2013 | P | PASS |
Daryl DeGrange
|
|
|
Floor box at east end of building, conduit running along north wall of building. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover interior under slab and floor box.
|
Electrical Rough-In | 9/20/2013 | 9/20/2013 | 9/20/2013 | P | PASS |
Daryl DeGrange
|
|
|
Underground inspect for Main Feeders. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover
|
Electrical Rough-In | 9/4/2013 | 9/5/2013 | 9/5/2013 | A | PASS |
Daryl DeGrange
|
|
|
This is a uffer ground inspection. Contact on the job is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover concrete encased electrode
|
Issue PAID IN FULL permit | | | 9/4/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/4/2013 | | DONE |
|
|
|
This permit was created on the web by Richard Montgomery
|