Final | 10/28/2013 | 10/29/2013 | 10/29/2013 | P | PASS |
Daryl DeGrange
|
|
|
Final Inspection on Shop. Tim ###-#### Phone #: ###-#### >> Inspection requested via web by Tim Lawrence final ok
|
Permanent Service | 10/24/2013 | 10/25/2013 | 10/25/2013 | P | PASS |
Daryl DeGrange
|
|
|
Permanent Service inspection Phone #: ###-#### >> Inspection requested via web by Tim Lawrence p/s o/h n ok
|
Permanent Service | 10/23/2013 | 10/24/2013 | 10/24/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Permanent Service Inspection Phone #: ###-#### >> Inspection requested via web by Tim Lawrence Not all corrections completed. Service Mask NEC 110.3 Mechanical strength and durability. Shall be made up with at least five threads fully engaged. 2" IMC has 12 threads, 9 threads are showing.
|
Permanent Service | 10/23/2013 | 10/23/2013 | 10/23/2013 | P | FAIL |
Doug A Poedy
|
|
|
Not enough mast threads in hub. Need to tie service to concrete encased electrode.
|
Final | 10/9/2013 | 10/11/2013 | 10/11/2013 | A | NH |
Doug A Poedy
|
|
|
New Shop Wiring Phone #: ###-#### >> Inspection requested via web by Tim Lawrence
|
Electrical Rough-In | 9/23/2013 | 9/24/2013 | 9/24/2013 | A | PASS |
Daryl DeGrange
|
|
|
3185 N. Wildwood. East on Ustick, South on Wildwood. House is located on the West corner of Ustick & Wildwood. Shop is located rear of Home. Phone #: ###-#### >> Inspection requested via web by Tim Lawrence rough-in ok cover detached garage
|
Issue PAID IN FULL permit | | | 9/23/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/23/2013 | | DONE |
|
|
|
This permit was created on the web by Tim Lawrence
|