Final | 1/21/2014 | 1/22/2014 | 1/22/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Final ok
|
Final | 1/20/2014 | 1/21/2014 | 1/21/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Chesnut 440.4- Over currect protective device shall be sized to nameplate rating , 25 amp max. 210.52- A receptical outlet shall be located at end of peninsula counter top. 310.12(C)- Conductors used as ungrounded conductors shall be clearly distinguishable from grounded conductors.
|
Rough-In Permanent Service | 10/4/2013 | 10/4/2013 | 10/4/2013 | P | PASS |
Rock A. Hudson
|
|
|
thanks Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 10/4/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/3/2013 | | |
|
|
|
|