Case Summary (ELE) | | | 10/3/2016 | | DONE |
|
|
|
|
First Notice | 11/15/2013 | 11/15/2013 | 5/22/2014 | | DONE |
Bob Reichert
|
|
|
|
Final | 11/15/2013 | 11/15/2013 | 11/15/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker corrections made, ok final
|
Final | 11/8/2013 | 11/12/2013 | 11/12/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker called, NEC 408.4 shall provide correct circuit schedule, 110.26 shall provide workspace about electrical equipment, both width and depth
|
Electrical Rough-In | 10/17/2013 | 10/17/2013 | 10/17/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker ri ok
|
Electrical Rough-In | 10/16/2013 | 10/17/2013 | 10/17/2013 | A | FAIL |
Bob Reichert
|
|
|
They are open for business so any time is fine Phone #: ###-#### >> Inspection requested via web by Brad Baker called, NEC 300.4(D) mc cable shall be 1 1/4" from edge of framing member
|
Issue PAID IN FULL permit | | | 10/16/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 10/16/2013 | | |
|
|
|
|
Application received | | | 10/16/2013 | | DONE |
|
|
|
This permit was created on the web by Brad Baker
|