Final | 2/13/2014 | 2/14/2014 | 2/14/2014 | A | PASS |
Bob Reichert
|
|
|
Garage code 3283 Phone #: ###-#### >> Inspection requested via web by daniel bibikov ok final
|
Final | 2/5/2014 | 2/6/2014 | 2/6/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.8- All garage 120 volt 15 and 20 amp recepticals shall have GFCI protection. 406.5- Switches and recepticals shall have faceplates installed. 406.4- Receptical yoke shall be rigidly mounted to box or box cover. 314.20- Boxes set back 1/4" or more shall have spark or extension ring.
|
Rough-In Permanent Service | 11/1/2013 | 11/1/2013 | 11/1/2013 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 10/31/2013 | 11/1/2013 | 11/1/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Corrections not complete, nail plate above pantry door and closet in spare bed and secure NM cable above trans box in garage
|
Rough-In Permanent Service | 10/30/2013 | 10/31/2013 | 10/31/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 300.4 NM csble shall be protected from physical damage where 1 1/4" not maintained from stud surface. 334.30- NM cabe shall be secured with in 12" of entering box with clamp, 8" with out. NM cable shall not be stapled on edge. BCC 4-05-23- It shall be unlawful to cover wiring before inspected.
|
Issue PAID IN FULL permit | | | 10/29/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/29/2013 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|