Permit Information
Permit NumberELE13-03025
StatusFinaled
Name R M E INC
Site Address 10700 W USTICK RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Reconnect power from old service.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice11/18/201311/18/201312/12/2013 DONE
DetailsDaryl DeGrange
This permit finaled on the web by Sean DeLacy
Temporary Service11/15/201311/18/201311/18/2013APASS
DetailsDaryl DeGrange
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy correction done, t/s o/h n ok
Temporary Service11/15/201311/15/201311/15/2013PFAIL
DetailsDaryl DeGrange
HP. Temp service. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Ground rod cut-off NEC Grounding electrode shall be at least 8ft. in contact with the soil.
Permanent Service10/30/201310/31/201310/31/2013PFAIL
DetailsDaryl DeGrange
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Idaho power Company requires pressure treated 6X6. NEC 230.24(B)(2) requires as least twelve feet clearance at drip loop. NEC 240.24 highest available location a circuit breakes can be installed is 6 ft. 7 inches
Issue PAID IN FULL permit  10/30/2013 DONE
Payment received via Govolutions
Application received  10/30/2013 DONE
This permit was created on the web by Sean DeLacy