First Notice | 11/18/2013 | 11/18/2013 | 12/12/2013 | | DONE |
Daryl DeGrange
|
|
|
This permit finaled on the web by Sean DeLacy
|
Temporary Service | 11/15/2013 | 11/18/2013 | 11/18/2013 | A | PASS |
Daryl DeGrange
|
|
|
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy correction done, t/s o/h n ok
|
Temporary Service | 11/15/2013 | 11/15/2013 | 11/15/2013 | P | FAIL |
Daryl DeGrange
|
|
|
HP. Temp service. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Ground rod cut-off NEC Grounding electrode shall be at least 8ft. in contact with the soil.
|
Permanent Service | 10/30/2013 | 10/31/2013 | 10/31/2013 | P | FAIL |
Daryl DeGrange
|
|
|
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Idaho power Company requires pressure treated 6X6. NEC 230.24(B)(2) requires as least twelve feet clearance at drip loop. NEC 240.24 highest available location a circuit breakes can be installed is 6 ft. 7 inches
|
Issue PAID IN FULL permit | | | 10/30/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/30/2013 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|