First Notice | 12/27/2013 | 12/27/2013 | 5/21/2014 | | DONE |
Daryl DeGrange
|
|
|
This permit finaled on the web by kendall bender
|
Final | 12/27/2013 | 12/27/2013 | 12/27/2013 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender final ok
|
Final | 12/26/2013 | 12/27/2013 | 12/27/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender NEC 210.08 (B) (5) Receptacles within 6 ft. of the outside edge of sink or basin require GFCI protection
|
Electrical Rough-In | 12/23/2013 | 12/24/2013 | 12/24/2013 | A | PASS |
Daryl DeGrange
|
|
|
NW area ceiling inspection for cover Phone #: ###-#### >> Inspection requested via web by kendall bender rough-in ok cover
|
Electrical Rough-In | 12/19/2013 | 12/20/2013 | 12/20/2013 | A | PASS |
Daryl DeGrange
|
|
|
Ceiling inspection south and break room. Phone #: ###-#### >> Inspection requested via web by kendall bender rough-in ok cover ceiling grid breakroom and area 1
|
Electrical Rough-In | 12/5/2013 | 12/6/2013 | 12/6/2013 | A | PASS |
Daryl DeGrange
|
|
|
wall ri at back entrance through door hard left, break room area. Phone #: ###-#### >> Inspection requested via web by kendall bender rough-in ok cover walls in rear office (north) entrance
|
Electrical Rough-In | 12/2/2013 | 12/3/2013 | 12/3/2013 | A | PASS |
Daryl DeGrange
|
|
|
Tim Phone #: ###-#### corrections done, p/s o/h rec ok
|
Electrical Rough-In | 12/2/2013 | 12/2/2013 | 12/2/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Mike Anderson Phone #: ###-#### NEC 330 .12(1) Subject to phyical damage, Less Than 1 1/4 to edge framing member. NEC 330.30 Securing MC cable with-in 12in. of box. Receptacle box requiring ko plugs
|
Electrical Rough-In | 11/21/2013 | 11/22/2013 | 11/22/2013 | P | PASS |
Bob Reichert
|
|
|
If possible please make us last stop Phone #: ###-#### >> Inspection requested via web by kendall bender se walls only ok cover
|
Issue PAID IN FULL permit | | | 11/13/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/13/2013 | | DONE |
|
|
|
This permit was created on the web by kendall bender
|