Permit Information
Permit NumberELE13-03181
StatusFinaled
Name BENDER ELECTRIC SERVICES
Site Address 10148 W EMERALD ST
Project NameWinCo Foods C2
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Remodel of office space relocation of lights and new partition walls
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice12/27/201312/27/20135/21/2014 DONE
DetailsDaryl DeGrange
This permit finaled on the web by kendall bender
Final12/27/201312/27/201312/27/2013PPASS
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by kendall bender final ok
Final12/26/201312/27/201312/27/2013AFAIL
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by kendall bender NEC 210.08 (B) (5) Receptacles within 6 ft. of the outside edge of sink or basin require GFCI protection
Electrical Rough-In12/23/201312/24/201312/24/2013APASS
DetailsDaryl DeGrange
NW area ceiling inspection for cover Phone #: ###-#### >> Inspection requested via web by kendall bender rough-in ok cover
Electrical Rough-In12/19/201312/20/201312/20/2013APASS
DetailsDaryl DeGrange
Ceiling inspection south and break room. Phone #: ###-#### >> Inspection requested via web by kendall bender rough-in ok cover ceiling grid breakroom and area 1
Electrical Rough-In12/5/201312/6/201312/6/2013APASS
DetailsDaryl DeGrange
wall ri at back entrance through door hard left, break room area. Phone #: ###-#### >> Inspection requested via web by kendall bender rough-in ok cover walls in rear office (north) entrance
Electrical Rough-In12/2/201312/3/201312/3/2013APASS
DetailsDaryl DeGrange
Tim Phone #: ###-#### corrections done, p/s o/h rec ok
Electrical Rough-In12/2/201312/2/201312/2/2013PFAIL
DetailsDaryl DeGrange
Mike Anderson Phone #: ###-#### NEC 330 .12(1) Subject to phyical damage, Less Than 1 1/4 to edge framing member. NEC 330.30 Securing MC cable with-in 12in. of box. Receptacle box requiring ko plugs
Electrical Rough-In11/21/201311/22/201311/22/2013PPASS
DetailsBob Reichert
If possible please make us last stop Phone #: ###-#### >> Inspection requested via web by kendall bender se walls only ok cover
Issue PAID IN FULL permit  11/13/2013 DONE
Payment received via Govolutions
Application received  11/13/2013 DONE
This permit was created on the web by kendall bender