Temporary Service | 12/2/2013 | 12/3/2013 | 12/3/2013 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov corrections made, t/s o/h n ok
|
Temporary Service | 11/24/2013 | 11/25/2013 | 11/25/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 230.24(B)(1) Lowest point of the drip loop for overhead service 10 ft. Idaho Power requires minimum 6x6 pressure treated for temp. overhead service.
|
Issue PAID IN FULL permit | | | 11/24/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/24/2013 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|